Field Notes · Step 03 · Validation

Trusting the data before using it

Circuit attribution and physical-plausibility checks are complete. Energy-balance closure against the utility meter is next.

Validation so far has two parts.

Does each circuit behave like what it feeds?

Every current sensor’s readings were checked against what its circuit should do: heat pumps that cycle with the weather, exterior lighting that wakes only after dusk, water heating that spikes and rests, an EV charger on a commuter’s schedule. A load with a predictable pattern makes a useful test. The electrician’s directory verification caught mislabeled circuits before they could corrupt the attribution.

Does the building add up?

Overnight, the HVAC panel goes quiet while the plug and process panels carry the night base load, so the building’s after-hours energy is on circuits the sensors measure.

Still to come

Energy-balance closure (the main service against the panels beneath it and against the utility meter), power-factor spot checks, and reconciliation with utility data. These are the checks that set up calibration of the energy model.

Lessons learned

  • Validate attribution the week of install, while the electrician’s notes are fresh.
  • Treat expected load signatures as test cases. A photocell circuit should look nocturnal.
  • Write the data-quality rules down as you find them. A dataset can only be defended if its rules are written down.